3
Date Code 20170814
Instruction Manual
SEL-700G Relay
SEL-700G Relay Command Summary
SER C
or
R
Clears SER data.
SER D
Displays SER delete report, which shows deleted items (use when SER auto-deletion is selected to remove
chatter).
SHO
n
Displays relay settings for group
n
(
n
= 1, 2, or 3). If
n
is not specified, default is the active settings group.
SHO F
Displays
front-panel
settings.
SHO G
Displays global settings.
SHO L
n
Displays general logic settings for group
n
(
n
= 1, 2, or 3). If
n
is not specified, default is the active settings
group.
SHO M
Displays Modbus User Map settings.
SHO P
n
Displays port settings, where
n
specifies the port (1, 2, 3, 4, or F);
n
defaults to the active port if not listed.
SHO R
Displays report settings.
STA
Displays relay self-test status.
STA S
Displays SEL
OGIC
usage status report.
SUM
Displays an event summary.
SUM R
or
C
Resets event summary buffer.
SYN
n
Displays generator synchronism-check report.
TAR
Displays default target row or the most recently viewed target row.
TAR
n
Displays target row
n
.
TAR
n
k
Displays target row
n
. Repeat display of row
n
for repeat count
k
.
TAR
name
Displays the target row with target name in the row.
TAR
name k
Displays the target row with target name in the row. Repeat display of this row for repeat count
k
.
TAR R
Resets any latched targets and the most recently viewed target row.
TIM
Views time.
TIM
hh:mm:ss
Sets time by entering
TIM
followed by hours, minutes, and seconds, as shown (24-hour clock).
TRI
Triggers an event report data capture.
Access Level 2 Commands
AST
Auto Start—starts generator automatic synchronizing control.
ASP
Auto Stop—stops generator automatic synchronizing control.
ANA
c p t
Tests analog output channel where
c
is the channel name or number,
p
is a percentage of full scale or either
letter “R” or “r” indicates ramp mode, and
t
is the duration of the test in decimal minutes.
BRE
n
R
Resets breaker data for breaker
n
, where
n
= X or Y.
BRE
n
W
Preloads breaker data for breaker
n
, where
n
= X or Y.
CAL
Enters Access Level C. If the main board access jumper is not in place, the relay prompts for the entry of
the Access Level C password. Access Level C is reserved for SEL use only.
CLO
n
Closes circuit breaker
n
, where
n
= X or Y.
CON RB
nn
k
Selects a remote bit to set, clear, or pulse where
nn
is a number from 01 to 32, representing RB01 through
RB32.
k
is S, C, or P for Set, Clear, or Pulse.
COP
m n
Copies relay and logic settings from Group
m
to Group
n
.
DTO
Downloads Volts/Hz user curve from SEL-5806 Curve Designer Software.
FIL WRITE
filename
Transfers settings file
filename
from the PC to the relay.
GEN
R
Resets generator operating statistics report data.
Serial Port Command
Command Description
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...