4.228
SEL-700G Relay
Instruction Manual
Date Code 20170814
Protection and Logic Functions
Front-Panel Settings (SET F Command)
Analog Display Point Entry Composition
In general, the legal syntax for analog display points consists of the following
two fields or strings:
Name, “User Text and Formatting.”
Unlike binary quantities, the relay displays analog quantities on both display
lines. Table 4.86 shows an entry in the Name string only (leaving the User
Text and Formatting string void) with the following syntax:
Figure 4.155 shows the front-panel display for the entry in Table 4.86, when
you use the SET F command, as follows:
Figure 4.155
Front-Panel Display for an Analog Entry in the
Name String Only
For a more descriptive name of the Relay Word bit, enter the Relay Word bit
in the Name String and an alias name in the User Text and Formatting String.
Table 4.87 shows a Boolean entry in the Name and Alias Strings (DP01) and
an entry in the Name and User Text and Formatting Strings (DP02), when you
use the SET F command, as follows:
where:
Name = Analog quantity name (AI301 for example). All analog
quantities occupy two lines on the front-panel display
(all binary quantities occupy one line on the display).
User text and
numerical
formatting
= Display the user text, replacing the numerical
formatting {width.dec, scale} with the value of Name,
scaled by “scale” formatted with total width “width”
and “dec” decimal places. Name can be either an analog
quantity or a Relay Word bit. The width value includes
the decimal point and sign character, if applicable. The
“scale” value is optional; if omitted, the scale factor
is 1. If the numeric value is smaller than the string size
requested, the string is padded with spaces to the left of
the number. If the numeric value does not fit within the
string width given, the string grows (to the left of the
decimal point) to accommodate the number.
Table 4.86
Analog Entry in the Name String Only
Name
Alias
Set String
Clear String
AI301
—
—
—
P01 := RID, “{16}”
?
AI301 <Enter>
DP01 := RID, “{16}”
?
IN101,"INPUT IN101:" <Enter>
DP02 := TID, “{16}”
?
AI301,TEMPERATURE: <Enter>
AI301
5.36 mA
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...