Overview
The SEL-700G Relay provides Phasor Measurement Unit (PMU) capabilities
when connected to an IRIG-B time source with an accuracy of ±10 µs or
better. Synchrophasor data are available via the MET PM ASCII command
and the C37.118 Protocol.
Synchrophasor measurement refers to the concept of providing measurements
taken on a synchronized schedule in multiple locations. A high-accuracy clock,
commonly called a Global Positioning System (GPS) receiver, such as the
SEL-2407 Satellite-Synchronized Clock, makes synchrophasor measurement
possible.
The availability of an accurate time reference over a large geographic area
allows multiple devices, such as SEL-700G relays, to synchronize the
gathering of power system data. The accurate clock allows precise event
report triggering and other off-line analysis functions. Synchrophasors are still
measured if the high-accuracy time source is not connected; however, the data
are not time-synchronized to any external reference, as indicated by Relay
Word bits TSOK := logical 0 and PMDOK := logical 0.
The SEL-700G Global settings class contains the synchrophasor settings,
including the choice of transmitted synchrophasor data set. The Port settings
class selects which serial port(s) or Ethernet port you can use for
synchrophasor protocol use. See Settings for Synchrophasors on page H.4.
The SEL-700G timekeeping function generates status Relay Word bits and
time-quality information that is important for synchrophasor measurement.
Some protection SEL
OGIC
variables, and programmable digital trigger
information is also added to the Relay Word bits for synchrophasors. See
Synchrophasor Relay Word Bits on page H.12.
When synchrophasor measurement is enabled, the SEL-700G creates the
synchrophasor data set at a user-defined rate. Synchrophasor data are available
in ASCII format over a serial port set to PROTO = SEL. See View
Synchrophasors Using the MET PM Command on page H.14.
The value of synchrophasor data increases greatly when the data can be shared
over a communications network in real time. A synchrophasor protocol is
available in the SEL-700G that allows for a centralized device to collect data
efficiently from several phasor measurement units (PMUs). Some possible
uses of a system-wide synchrophasor system include the following:
➤
Power-system state measurement
➤
Generator Model Validation
➤
Wide-area network protection and control schemes
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...