F.28
SEL-700G Relay
Instruction Manual
Date Code 20170814
IEC 61850 Communications
Logical Nodes
Table F.17 shows the LN associated with measuring elements defined as
Logical Device MET.
S1PTOV13
Op.general
59S1T
Level 1 sync overvoltage element trip
S1PTOV13
Str.general
59S1
Level 1 sync overvoltage element pickup
S1PTOV13
Str.dirGeneral
unknown
Direction undefined
S1PTUV7
Op.general
27S1T
Level 1 sync undervoltage element trip
S1PTUV7
Str.general
27S1
Level 1 sync undervoltage element pickup
S1PTUV7
Str.dirGeneral
unknown
Direction undefined
S2PTOV14
Op.general
59S2T
Level 2 sync overvoltage element trip
S2PTOV14
Str.general
59S2
Level 2 sync overvoltage element pickup
S2PTOV14
Str.dirGeneral
unknown
Direction undefined
S2PTUV8
Op.general
27S2T
Level 2 sync undervoltage element trip
S2PTUV8
Str.general
27S2
Level 2 sync undervoltage element pickup
S2PTUV8
Str.dirGeneral
unknown
Direction undefined
T49PTTR2
Op.general
49T
Thermal trip, generator thermal capacity above Level 1
TRIP1PTRC3
Tr.general
TRIP1
Generator field breaker trip
TRIP2PTRC4
Tr.general
TRIP2
Prime mover trip
TRIP3PTRC5
Tr.general
TRIP3
Generator lockout breaker trip
TRIPXPTRC1
Tr.general
TRIPX
X-side (generator main circuit) breaker trip
TRIPYPTRC2
Tr.general
TRIPY
Y-side breaker trip
Z40PDUP1
Op.general
40Z1T
Zone 1 time-delayed loss-of-field mho element
Z40PDUP1
Str.general
40Z1
Zone 1 instantaneous loss-of-field mho element
Z40PDUP1
Str.dirGeneral
unknown
Direction undefined
Z40PDUP2
Op.general
40Z2T
Zone 2 time-delayed loss-of-field mho element
Z40PDUP2
Str.general
40Z2
Zone 2 instantaneous loss-of-field mho element
Z40PDUP2
Str.dirGeneral
unknown
Direction undefined
a
Writing a 0 to BnCSWIm.CO.Pos.Oper.ctlVal will cause OCn to assert and writing any other value will cause CCn to assert; (n = X or Y) and
(m = 1 or 2).
b
Data validity depends on the relay model and installed card options. Refer to Section 1: Introduction and Specifications for different relay
models and available card options.
c
If the breaker/contactor is closed, value = 10(2); if the breaker/contactor is opened, value = 01(1).
Table F.16
Logical Device: PRO (Protection)
(Sheet 11 of 11)
Logical Node
Attribute
Data Source
Comment
Table F.17
Logical Device: MET (Metering)
(Sheet 1 of 7)
Logical Node
Attribute
Data Source
Comment
Functional Constraint = DC
DevIDLPHD1
PhyNam.model
PARTNO
Part number
Functional Constraint = Mx
ab
METXMDST1
DmdA.phsA.instCVal.mag.f
IAXD
X-Side Phase A current demand
METXMDST1
DmdA.phsB.instCVal.mag.f
IBXD
X-Side Phase B current demand
METXMDST1
DmdA.phsC.instCVal.mag.f
ICXD
X-Side Phase C current demand
METXMDST1
DmdA.res.instCVal.mag.f
IGXD
X-Side residual current demand
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...