10.6
SEL-700G Relay
Instruction Manual
Date Code 20170814
Testing and Troubleshooting
Commissioning Tests
Connection Tests
Step 1. Remove control voltage and ac signals from the SEL-700G by
opening the appropriate breaker(s) or removing fuses.
Step 2. Isolate the relay contact assigned to be the
TRIP
output.
Step 3. Verify correct ac and dc connections by performing point-to-
point continuity checks on the associated circuits.
Step 4. Apply ac or dc control voltage to the relay.
After the relay is energized, the front-panel green
ENABLED
LED
should illuminate.
Step 5. Use the appropriate serial cable (SEL cable C234A or
equivalent) to connect a PC to the relay.
Step 6. Start the PC terminal emulation software and establish
communication with the relay.
Refer to Section 7: Communications for more information on
serial port communications.
Step 7. Set the correct relay time and date by using either the front-
panel or serial port commands (TIME hh:mm:ss and DATE
mm/dd/yy commands).
Step 8. Using the SET, SET P, SET G, SET L, and SET R serial port
commands, enter the relay settings from the settings sheets for
your application.
If you are connecting an external SEL-2600 RTD Module or
SEL-2664 Field Ground Module, follow the substeps below;
otherwise continue with Step 9.
a. Connect the fiber-optic cable to the RTD module or
field ground module fiber-optic output.
b. Plug the relay end of the fiber-optic cable into the relay
fiber-optic Rx input (Port 2). For an SEL-2600
application, use Port 2; for an SEL-2664 application,
use Port 3.
Step 9. Verify the relay ac connections.
Step 10. Connect the ac test source current or voltage to the appropriate
relay terminals.
NOTE:
Make sure that the current
transformer secondary windings are
shorted before they are disconnected
from the relay.
a. Disconnect the current transformer and voltage
transformer (if present) secondaries from the relay prior
to applying test source quantities.
b. If you set the relay to accept phase-to-ground voltages
[DELTAY_m := WYE (m = X or Y)], set the current
and/or voltage phase angles as shown in Figure 10.3.
c. If you set the relay to accept delta voltages
[(DELTAY_m := DELTA (m = X or Y)], set the current
and/or voltage phase angles as shown in Figure 10.4.
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...