SET.2
of 68
SEL-700G Relay
Instruction Manual
Date Code 20170814
SEL-700G Settings Sheets
Group Settings (SET Command)
Other
SYNCV PT RATIO (1.00–10000.00) (Hidden if Slot
E
= Empty/73/77)
PTRS :=
NEUT CT RATIO (1–10000 [5 A I
NNOM
], 1–50000 [1 A I
NNOM
])
(Hidden if Slot
Z
= 83/87)
CTRN :=
NEUT PT RATIO (1.00–10000.00) (Shown if Slot
E
= 74/ 72/76)
PTRN :=
Generator Differential
(Hidden if Slot E = Empty/ 74/71/ 75)
PHASE DIFF EN (GEN, TRANS, NONE)
E87 :=
Note:
(
All Differential settings are hidden if E87 := NONE.)
MAX XFMR CAP (OFF, 0.2–5000.0 MVA) (Hidden and auto-set to OFF if E87 := GEN)
MVA :=
DEFINE CT COMP (Y, N) (Hidden and auto-set to N if E87 := GEN)
ICOM :=
X SIDE CT COMP (0, 12) (Hidden and automatically set to 0 if ICOM := N)
CTCX :=
Y SIDE CT COMP (0, 1, 5, 6, 7, 11, 12) (Hidden and auto-set to 0 if ICOM := N)
CTCY :=
WDG-X L-L VOLTS (0.2–1000.0 kV) (Hidden if MVA := OFF)
VWDGX :=
WDG-Y L-L VOLTS (0.2–1000.0 kV) (Hidden if MVA := OFF)
VWDGY :=
X SIDE CURR TAP (0.5–31.0 A [5 A I
XNOM
]; 0.1-6.2 A [1 A I
XNOM
]) (Auto-set if MVA
setting is not OFF)
TAPX :=
Y SIDE CURR TAP (0.5–31.0 A [5 A I
YNOM
]; 0.1-6.2 A [1 A I
YNOM
]) (Auto-set if MVA
setting is not OFF)
TAPY :=
OPERATE CURR LVL (0.10–1.00 TAP)
O87P :=
UNRES CURR LVL (1.0–20.0 TAP)
U87P :=
DIFF CURR AL LVL (OFF, 0.05–1.00 TAP)
87AP :=
DIFF CURR AL DLY (1.00–120.00 s) (Hidden if O87P := OFF)
87AD :=
RESTRAINT SLOPE1 (5–70 %)
SLP1 :=
RESTRAINT SLOPE2 (5–90 %) (Hidden and auto-set to 70 if E87 := GEN)
SLP2 :=
RES SLOPE1 LIMIT (1.0–20.0 TAP) (Hidden and auto-set to 6.0 if E87 := GEN)
IRS1 :=
2ND HARM BLOCK (OFF, 5–100 %) (Hidden and auto-set to OFF if E87 := GEN)
PCT2 :=
4TH HARM BLOCK (OFF, 5–100 %) (Hidden and auto-set to OFF if E87 := GEN)
PCT4 :=
5TH HARM BLOCK (OFF, 5–100 %) (Hidden and auto-set to OFF if E87 := GEN)
PCT5 :=
5TH HARM AL LVL (OFF, 0.02–3.20 TAP) (Hidden and auto-set to OFF if E87 := GEN)
TH5P :=
5TH HARM AL DLY (0.00–120.00 s) (Hidden if TH5P := OFF)
TH5D :=
HARMONIC RESTRNT (Y, N) (Hidden and auto-set to N if E87 := GEN)
HRSTR :=
HARMONIC BLOCK (Y, N) (Hidden and auto-set to Y if E87 := GEN)
HBLK :=
HI SECURITY MODE (SEL
OGIC
)
HSM :=
HI SECURITY PU (AUTO, O87P–2.00) (AUTO in the setting range is hidden if
E87 := GEN. The value of O87P2 must be greater than or equal to O87P.)
O87P2 :=
EXT FLT DET DO (1.00–30.00 s)
HSMDOT :=
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...