SET.9
of 68
Date Code 20170814
Instruction Manual
SEL-700G Relay
SEL-700G Settings Sheets
Group Settings (SET Command)
EM RESET DELAY (Y, N) (Hidden if 51PXP := OFF)
51PXRS :=
CONST TIME ADDER (0.00–1.00 s) (Hidden if 51PXP := OFF)
51PXCT :=
MIN RESPONSE TIM (0.00–1.00 s) (Hidden if 51PXP := OFF)
51PXMR :=
PH TOC TRQCTRL (SEL
OGIC
) (Hidden if 51PXP := OFF)
51PXTC :=
X-Side Residual Time-Overcurrent
(Hidden if Slot Z = 84/88 or CTCONX := Delta)
RES TOC LEVEL (OFF, 0.50–16.00 A [5 A I
XNOM
], 0.10–3.20 A [1 A I
XNOM
])
51GXP :=
RES TOC CURVE (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) (Hidden if 51GXP := OFF)
51GXC :=
RES TOC TDIAL (0.50–15.00 [if 51G_C := U_], 0.05–1.00 [if 51G_C := C_])
(Hidden if 51GXP := OFF)
51GXTD :=
EM RESET DELAY (Y, N) (Hidden if 51GXP := OFF)
51GXRS :=
CONST TIME ADDER (0.00–1.00 s) (Hidden if 51GXP := OFF)
51GXCT :=
MIN RESPONSE TIM (0.00–1.00 s) (Hidden if 51GXP := OFF)
51GXMR :=
RES TOC TRQCTRL (SEL
OGIC
) (Hidden if 51GXP := OFF)
51GXTC :=
X-Side Negative-Sequence Time-Overcurrent
(Shown if Slot Z = 83/87 [700GW])
NSEQ TOC LEVEL (OFF, 0.50–16.00 A [5 A I
XNOM
], 0.10–3.20 A [1 A I
XNOM
])
51QXP :=
NSEQ TOC CURVE (U1, U2, U3, U4, U5, C1, C2, C3, C4, C5)
(Hidden if 51QXP := OFF)
51QXC :=
NSEQ TOC TDIAL (0.50–15.00 [if 51Q_C := U_], 0.05–1.00 [if 51Q_C := C_])
(Hidden if 51QXP := OFF)
51QXTD :=
EM RESET DELAY (Y, N) (Hidden if 51QXP := OFF)
51QXRS :=
CONST TIME ADDER (0.00–1.00 s) (Hidden if 51QXP := OFF)
51QXCT :=
MIN RESPONSE TIM (0.00–1.00 s) (Hidden if 51QXP := OFF)
51QXMR :=
NSEQ TOC TRQCTRL (SEL
OGIC
) (Hidden if 51QXP := OFF)
51QXTC :=
Y-Side Phase Time-Overcurrent
(Shown if Slot E = 71/ 73/75/ 77 [700GT, 700GW])
PHASE TOC LEVEL (OFF, 0.50–16.00 A [5 A I
YNOM
], 0.10–3.20 A [1 A I
YNOM
])
51PYP :=
PHASE TOC CURVE
(U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) (Hidden if 51PYP := OFF)
51PYC :=
PHASE TOC TDIAL (0.50–15.00 [if 51P_C := U_],
0.05–1.00 [if 51P_C := C_]) (Hidden if 51PYP := OFF)
51PYTD :=
EM RESET DELAY (Y, N) (Hidden if 51PYP := OFF)
51PYRS :=
CONST TIME ADDER (0.00–1.00 s) (Hidden if 51PYP := OFF)
51PYCT :=
MIN RESPONSE TIM (0.00–1.00 s) (Hidden if 51PYP := OFF)
51PYMR :=
PH TOC TRQCTRL (SEL
OGIC
) (Hidden if 51PYP := OFF)
51PYTC :=
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...