74
A-01
Wobble Frequency input mode
Factory setting
d 0
Setting range
d 0
Set according to wobble frequency action delay
d 1
Controlled by external terminals.
This parameter is to set input mode of wobble frequency:
When it is set to d0, it shall be input automatically. In this case, it shall firstly run for a period (A-03) in wobble
frequency preset frequency (A-02) after starting, and then wobble frequency shall be realized automatically.
When it is set to d1, it shall be controlled manually by external terminals. Which means that wobble frequency shall
be realized when multifunction terminal (Function 27 is for wobble frequency input) available; while wobble frequency
shall not exist when terminal unavailable, with running frequency kept at wobble frequency preset frequency A-02.
A-02
Pre-set frequency of Wobble Frequency
Factory setting
d 0.0
Setting range
d 0.0<->d 400Hz
Unit
0.1Hz
Operation frequency of the inverter prior to wobble frequency running status shall be determined by this parameter.
A-03
Action delay setting of preset Wobble Frequency
Factory setting
d 0.0
Setting range
d 0.0<->d 600s
Unit
0.1s
When auto-restarting is in option, A-30 is to set the delay time running in preset frequency of wobble frequency; and
it shall be unavailable when inverter is set to manually control mode.
A-04
Central frequency of Wobble Frequency
Factory setting
d 0
Setting range
d 0
According to operation frequency source
d 1
According to fixed frequency setting(A-05)
A-05
Fixed central frequency setting of Wobble Frequency
Factory setting
d 20.0
Setting range
d
0.01<->d
100%
(Corresponding
Maximum
Frequency Operation)
Unit
0.1%
A-06
Reference source setting for wobble aptitude
Factory setting
d 0
Setting range
d 0
Centering frequency base
d 1
Max frequency(1-00) base
Wobble frequency running is limited by min and max setting. Fault shall occur if it is not set properly.
A-07
Wobble aptitude width setting
Factory setting
d 0.0
Setting range
d 0.0<->d 50.0%
Unit
0.1%
Wobble amplitude shall be calculated according to Parameter A-06.