30
8. High Function Parameters
Set during running available
Parame
ter
Parameter functions
Setting range
Factory
setting
8-19
Reserved
8-20
Auto-reset(Counter clear time)
1 to 100 min
10
8-21
Reserved
8-22
Auto-reset(Reset interval)
0.1 to 20.0s
2.0
Parameters marked with “reserved” will be displayed, but will not be used for the inverter. Please do not change the
code of such kind of parameter.
9. Communications Parameters
Set during running available
Parame
ter
Parameter functions
Setting range
Factory
setting
9-00
RS485 Communications Station
address (Station address)
1 to 247
1
9-01
Baud rate
0:Baud rate 4800 bps
1:Baud rate 9600 bps
2:Baud rate 14400 bps
3:Baud rate 19200 bps
4:Baud rate 38400 bps
1
9-02
Communications error processing
0:Warning and running continuously
1:Warning and deceleration to stop
2:Warning and coasting to a stop
3:No warning and running continuously
0
9-03
No-response error detection time
0: Not detected
1 to 20s
0
9-04
(Communications format )
<Data length, Parity, STOP bit>
0: ASSII mode <8, N,1>
1: ASSII mode <8, N,2>
2: ASSII mode <8, E,1>
3: ASSII mode <8, E,2>
4: ASSII mode <8, O,1>
5: ASSII mode <8, O,2>
6: RTU mode <8, N,2>
7: RTU mode <8, E,1>
8: RTU mode <8, O,1>
9 to 11 :Reserved
0
9-05
Reserved
9-06
Reserved
9-07
Response interval
0 to 200 (one unit=2ms)
1
Parameters marked with “reserved” will be displayed, but will not be used for the inverter. Please do not change the
code of such kind of parameter.