67
Command code: 06H, write for one character (word), for example: write 6000(1770H) to address 0100H of inverter in
01H for address.
ASC
Ⅱ
Mode:
Command
STX
‘:’
ADR1
‘0’
ADR0
‘1’
CMD 1
‘0’
CMD0
‘6’
Data address
‘0’
‘1’
‘0’
‘0’
Data
‘1’
‘7’
‘7’
‘0’
LRC CHK 1
‘7’
LRC CHK 0
‘1’
END 1
CR
END 0
LF
Response
STX
‘:’
ADR1
‘0’
ADR0
‘1’
CMD 1
‘0’
CMD0
‘6’
Data address
‘0’
‘1’
‘0’
‘0’
Data
‘1’
‘7’
‘7’
‘0’
LRC CHK 1
‘7’
LRC CHK 0
‘1’
END 1
CR
END 0
LF
RTU Mode
Command
ADR
01H
CMD
06H
Data address
01H
00H
Data
17H
70H
CRC CHK Low
86H
CRC CHK High
22H
Response
ADR
01H
CMD
06H
Data address
01H
00H
Data
17H
70H
CRC CHK Low
86H
CRC CHK High
22H