37
1-13
Acceleration time (JOG)
Factory setting
d 10.0
Setting Range
d 0.01<->d 600s
Unit
0.01s
1-14
Deceleration time (JOG)
Factory setting
d 10.0
Setting Range
d 0.01<->d 600s
Unit
0.01s
1-15
JOG frequency setting
Factory setting
d 6.0
Setting Range
d 1.0<->d 400Hz
Unit
0.01Hz
Multi-functional input terminal (one from FWD, REV, MI3~MI5) shall be set as jog operation when jog function is used.
If switches connected with JOG function are CLOSED, inverter shall accelerate from min operation frequency (1-05)
to jog operation frequency (1-15). Accel/decel time of jog run is determined with reference time set by parameter
(1-13/1-14). Jog run reference also can be performed while inverter is in operation. The inverter will return to the
original operation frequency after canceling the jog-on command. B
ut other operation commands can’t be performed
in jog operation.
1-16
Reserved
1-17
Reserved
1-18
Reserved