42
2-10
Rotation direction inhibition
Factory setting
d 0
Setting range
d 0: Fwd / Rev run available
d 1: Rev run inhibited
d 2: Fwd run inhibited
If parameter is set to d1” Reverse run inhibited”, REV reference of both the operation keypad and external terminals
shall be unavailable. Even if Rev Run is performed currently, it shall be switched to fwd run directly. Also, provided
that fwd run is inhibited, only Rev run reference shall be performed.
2-11
Reference loss detection(Terminal ACI)( stop mode)
Factory setting
d 0
Setting range
d0: Non-processing
d1: Coast to stop
d2: EF display after deceleration stop
d3: Continuous operation by reference frequency before disconnection
Treatment to reference of 4~20mA (ACI) broken line is determined by this parameter. If it was set to d2 and fault
occurs, press MODE/RESET to reset after alarm is eliminated.
2-12
Power on start
Factory setting
d 0
Setting range
d 0: Operation available
d 1: Operation unavailable
When operation reference is from external terminal and operation reference is always in kept station, and when
power supply of inverter is starting, this parameter is to determine operation status of motor. If it is set to d0,
operation reference shall be accepted and motor begin to run; if it is set to d1, the operation reference shall be
rejected and motor coast to a stop. To start the motor running, operation reference shall be firstly cancelled and then
input again.
Due to mechanical vibration or switch bouncing which may be caused by switch parts fault, operation may be not
inhibited although this parameter is set to 1. Thus great care shall be attached when using this function.
2-13
Reserved
2-14
Reserved