9
E
n
v
iro
n
m
e
n
t
Operational Environment
temperature
-10
℃
to +50
℃
(+40
℃
parallel installation, no condensation, no
freezing)
Storing temperature
-20
℃
to +60
℃
Operational Environment dampness
Below 90%RH without moister
Installation height
Lower than 1000m, without corrosive gas, fluid and dust.
Vibration
Under 20Hz 9.80665m/s
2
(1g), 20 to 50Hz 5.88 m/s
2
(0.6g)
Protection level
IP20
SAVCH ELECTRIC shall not be responsible for faults due to the following:
(1) Absence or inapplicable or over large non-fuse breakers was put between the power supply and the inverter,
which results in the inverter fault.
(2) Magnetic contactors or advance capacitor or Surge Absorber were connected in series between the inverter and
motor.
● A three phase squirrel-cage induction motor which corresponds with the capacity of the inverter shall be adopted.
● If more than one motors were driven simultaneously by one inverter, the current of these motors when running shall
below capacity of the inverter. And each motor shall be prepared with a thermal relay in appropriate capacity.
● Phase advance capacitors and other capacity elements such as LC or RC shall not be fixed between the inverter
and motor.
4. LIST OF APPLICABLE NO-FUSE BREAKER
The wire size recommended to main circuit terminals is to use single-stranded HIV wire (max. allowable temperature
75
℃
) under ambient temperature of 40
℃
. The content in ( ) is the example of single-stranded IV wire (max.
allowable temperature 60
℃
).
Type
S900-2S
single-phase series
Suitable
power of
motor (kW)
Rated
current of
breaker (A)
Main circuit (mm
2
)
Control
circuit (mm
2
)
Input wire
Positive and
negative bus
Output
wire
Grounding
wire
Control
terminal wire
S900-2S0.2G
0.2
10
1
1
1
2
1
S900-2S0.4G
0.4
15
1.5
1
1
2
1
S900-2S0.75G
0.75
20
2.5
1
1
2
1
S900-2S1.5G
1.5
40
4
1.5
2.5
2
1
S900-2S2.2G
2.2
50
5.5
1.5
2.5
2
1
Type
S900-4T
three-phase series
Suitable
power of
motor (kW)
Rated
current of
breaker (A)
Main circuit (mm
2
)
Control circuit
(mm
2
)
Input wire
Positive and
negative bus
Output wire
Grounding
wire
Control
terminal wire
S900-4T0.4G
0.4
5
1
1
1
22
1
S900-4T0.75G
0.75
10
1
1
1
22
1
S900-4T1.5G
1.5
15
1.5
1
1.5
22
1
S900-4T2.2G
2.2
15
1.5
1.5
1.5
22
1
S900-4T3.7G
3.7
20
2.5
1.5
2.5
22
1