36
1-07
Frequency limiter(Upper)
Factory setting
d 100
Setting range
d 1<->d 110%
Unit
1%
1-08
Frequency limiter(Lower)
Factory setting
d 0
Setting range
d 0<->d 100%
Unit
1%
The % value of the above two parameters shall take Parameter 1-00 for reference.
The min as well as max values are mainly set to prevent mishandling of operators, thus protecting motor from
overheating caused by over-low running frequency, or mechanical wearing by an over-high speed.
If max output frequency is set to 80%, and frequency set to (1-00) 60Hz, then max output frequency shall be 48Hz. If
min output frequency is set to 10%, while Min operation frequency (1-05) set to 1.5Hz, it shall run in 6Hz in case of
set frequency is below 6Hz.
1-09
Acceleration time 1
Factory setting
d 10.0
1-10
Deceleration time 1
Factory setting
d 10.0
1-11
Acceleration time 2
Factory setting
d 10.0
1-12
Deceleration time 2
Factory setting
d 10.0
Setting range
d 0.01<->d 600S
Unit
0.01S
The acceleration time during inverter acceleration and deceleration shall be the time used for accelerating from 0Hz
to Max output frequency (1-00); while deceleration time refers to the time for deceleration from Max output frequency
(1-00) to 0Hz.
Applying the 2nd accel/decel time shall be available after the multi-functional terminals are set to switching of 1st and
2nd accel/decel. 2nd accel/ shall be performed when terminals for this function are closed.
As the diagram shows below, the motor adopts area of max output frequency (1-00) from 0Hz for acceleration and
deceleration calculation, If 1-00 is 60.0Hz. Provided that min frequency is 1.0Hz, time for accelerating to 60Hz shall
be 9.83sec, and deceleration to stop shall also be 9.83sec.