1. BASIC PARAMETERS
1-00
Maximum frequency
Factory setting
d 50.0
Setting range
d 5.0<->d 400Hz
Unit
0.1Hz
To set max output frequency of the inverter. Range of this frequency is corresponded to digital operation keypad
frequency and all the other analog input frequency setting signals (0 to +10V, 4 to 20mA).
1-01
Base frequency
Factory setting
d 50.0
Setting range
d 10.0<->d 400Hz
Unit
0.1Hz
This setting value must be in accordance with the rated frequency on the motor nameplate.
1-02
Rated voltage at base frequency
Factory setting
d 220*
Setting range
d 2.0<->d 255V*
Unit
0.1V
It is used to set max output voltage of the inverter. This setting shall be in accordance with rated motor voltage
explained on the nameplate.
1-03
Intermediate frequency setting
Factory setting
d 1.0
Setting range
d 0.1<->d 400Hz
Unit
0.1Hz
This parameter shall be used to set intermediate frequency for a random V/f curve. V/f ratio of Min frequency to
Intermediate frequency shall be determined by this setting.
1-04
Intermediate voltage setting
Factory setting
d 12.0*
Setting range
d 2.0<->d 255V*
Unit
0.1V
This parameter shall be used to set intermediate voltage for a random V/f curve. V/f ratio of Min output voltage to
Intermediate voltage shall be determined by this setting.
1-05
Starting frequency
Factory setting
d 1.00
Setting range
d 0.1<->d 60.0Hz
Unit
0.0Hz
For setting Min output frequency of inverter.
1-06
Output voltage at starting frequency
Factory setting
d 12.0*
Setting range
d 2.0<->d 255V*
Unit
0.1V
For setting Min output voltage of AC motor drive.
Setting of 1-01 to 1-06 shall be input only if the following requirements be met: 1-
02≥1-04≥1-06; 1-01≥1-03≥1-05,
and according to different voltage classes, voltage of 1-02, 1-04 and 1-06 shall display corresponding voltage values.