This function is set for uncertain load inertia circumstances. Deceleration over voltage shall not occur in normal load
stop, and deceleration time shall also be applicable. However, tripping shall not occur due to over voltage in
occasional load back up inertia increase stop; in these occasions, deceleration time shall be increased automatically
by the inverter to stop. This function is inapplicable provided that deceleration time disturbs application. This problem
shall be solved by increasing deceleration time or install braking module to absorb excessive back up voltage.
6-01
Over current stall prevention level setting
Factory setting
d 170
Setting range
d 0
Inactive
d 1
d 20<->d 200%
Unit
1%
During operation of AC motor drive, provided that output current exceeds set value of 6-01 (Over current stall
prevention current level during running), output frequency shall be decreased by AC motor drive to prevent motor
stalling. AC motor drive shall perform acceleration again to set frequency when output current is below setting of 6-01.
Set unit shall be percentage of rated output current (100%) of the AC motor drive.
Over current stall prevention function during running
Overvoltage
detection level
DC side voltage
Overvoltage stall prevention function
Output frequency
Time
Time
Output current
Stalling overcurrent
detection level
Output frequency
Time
Time
6-01