45
2. When it is set to d17, d18 and d19, once stop signal appears, relay shall be interrupted immediately. See
sequence diagram below:
Fwd run reference delay time
FWD and REV run stations
0: Fwd run 1: Rev run
Relay output
0: Open 1:Closed
Rev run reference delay time
3-06
Analog output setting
Factory setting
d0
Setting range
d0: Output frequency 1 (before slip compensation)
d1: Output frequency 2 (after slip compensation)
d2: Analog current meter(0 to 250% of rated current)
d3: Analog output voltage
d4: Analog DC bus voltage
d5: Input power
This parameter select inverter analog signal voltage (0~+10VDC, up to +11V) to output the corresponding content,
which is as shown in table below:
Setting value
Analog content
Max. value of output voltage corresponds to :
d0
Output frequency 1 (before slip compensation)
Maximum frequency
(
1-00
)
d1
Output frequency 2 (after slip compensation)
Maximum frequency
(
1-00
)
d2
Analog current meter(0 to 250% of rated current)
250% rated current
d3
Analog output voltage
200V series:250V
400V series: 500V
d4
Analog DC bus voltage
200V series:500V
400V series: 1000V
d5
Input power
200% inverter rated output
3-07
Reserved
3-08
Analog output gain selection
Factory setting
100
Setting range
d1 to d200%
Unit
1%
This parameter adjusts voltage level of inverter analog signal output terminal FMA output to analog meter head.