33
0-01
Rated current display of inverter (only for reading)
Factory setting
d#.#
Setting range
Non
This parameter displays the rated current of inverter, corresponding to machine types displayed at Parameter 0-00.
0-02
Data initialization
Factory setting
d 0
Setting range
d 0<->20
No action
d 10
All parameters reset to factory setting
This parameter enable users to reset all parameters to factory setting.
0-03
Machine On display Selection
Factory setting
d 0
Setting range
d 0
F (Displaying set frequency reference)
d 1
H (Displaying actual running frequency)
d 2
U (Displaying multifunctional definitions)
d 3
A (Displaying motor running current)
This parameter enables users to determine the machine ON display by themselves.
0-04
Determining multifunctional display
Factory setting
d 0
Setting range
d 0
Displaying output physical quantity(u) defined by operators
d 1
Displaying count value (c)
d 2
Displaying program operation content (X=tt)
d 3
Displaying DC-BUS voltage(U)
d 4
Displaying output voltage (E)
d 5
Displaying rotating speed(r )
d 6
Output frequency 2 (after slip compensation) (h)
d 7
Input power (P)
d8<->d15 Reserved
Output physical quantity defined by users shall be displayed when it is set to d0 (Physical quantity =H×0-05)
0-05
Proportional constant setting
Factory setting
d 1.0
Setting range
d 0.1<->d 160
Unit
0.1
Proportional constant K, the constant used in output physical quantity defined by users.
This parameter should be used in conjunction with d0, d5 and d6 of 0-04.
The display value shall be counted as this formula shown below:
When set 0-04 as d0, display value= Output frequency (before slip compensation) x K (0-05)
When set 0-04 as d5 display value= rotating speed x K (0-05).
When set 0-04 as d6, display value= Output frequency 2 (after slip compensation) x K (0-05).