46
3-09
Terminal [MO1] Function
Factory setting
1
Setting range
d0
No function
d1
Inverter running
d2
Frequency arrival
d3
Zero-speed
d4
Over torque detection
d5
During external alarm
d6
Low voltage detection
d7
External terminal running mode
d8
Alarm output (for any alarm)
d9
Frequency detection
d10
During pattern operation
d11
Pattern operation one cycle completion
d12
Pattern operation completion
d13
Pattern operation pause
d14
Terminal count value arrival
d15
Terminal designated count value arrival
d16
Inverter ready to run
d17
Fwd running
d18
Rev running
d19
Fwd/ Rev running direction
This function corresponds to external terminal MO1, CM (open-collector output). Different system signals output can
be obtained if set value of 3-09 as per above table. The function description is same to that in 3-05.
3-10
Reserved
3-11
Dead time setting of Fwd and Rev changeover
Factory setting
d 0.0
Setting range
d 0.0 <-> d 600s
Unit
0.1s
This parameter is used to set FWD/REV switching interval.
3-12
Cooling fan control
Factory setting
d 0
Setting range
d 0
Fan continuous running
d 1
Run for 1 minute after pressing stop key
d 2
Operate/stop along with diver
This parameter determines the action mode of cooling fan.
3-13
Bias [AVI] (Bias base point)
Factory setting
d 0.0
Setting range
d 0.0<-> d 10.0V
Unit
0.1V
3-14
Bias [AVI] (Bias value)
Factory setting
d 0.0%
Setting range
d 0.0%<-> d 100% of Maximum Frequency
Unit
0.1%
3-15
Analog input Adjustment for [AVI] (Gain base point)
Factory setting
d 10.0
Setting range
d 0.0<-> d 10.0V
Unit
0.1V