58
6-07
Alarm history (Latest)
Factory setting
d 0
6-08
Alarm history (1
st
last)
Factory setting
d 0
6-09
Alarm history (2
nd
last)
Factory setting
d 0
6-10
Alarm history (3
rd
last)
Factory setting
d 0
6-11
Alarm history (4
th
last)
Factory setting
d 0
6-12
Alarm history (5
th
last)
Factory setting
d 0
Setting range
Non
Parameter 6-07~ 6-12 is available to record alarm signals of recent six times. Inverter shall be reset to prepared
station provided that alarm has been eliminated. Records of 6 times shall not be reset to factory setting due to
parameter reset.
Value meaning
d0
No fault records
d14
Reserved
d1
OC ( over current)
d15
Reserved
d2
OV (over voltage)
d16
CF2(Read error of internal storage IC data)
d3
OH (over heating)
d17
External alarm signal input
d4
OL(Inverter overload)
d18
OL2(Motor overload)
d5
OL1(Motor overload)
d19
Reserved
d6
EF(External alarm)
d20
Reserved
d7
Reserved
d21
Reserved
d8
Reserved
d22
CF3.1(Internal temperature is over high or circuit alarm at power-on test)
d9
Reserved
d23
CF3.2(Over voltage of internal DC voltage side at power-on test)
d10
Reserved
d24
CF3.3(Under voltage of internal DC voltage side at power-on test)
d11
Reserved
d29
HPF.1 (Over voltage protection circuit alarm)
d12
Reserved
d31
HPF.3 (Over current protection circuit alarm)
d13
Reserved
d37
Errb (Wobble frequency setting error)
60Hz or more
50Hz
10Hz
5Hz
Operation
time (min)
5
2
1
0
20 40 60 80 100 120 140 160 180 200
3
4
Load
factor (
﹪
)