44
Function List
Set
value
Description of function
d 0
No function
d 1
Inverter running. If output occurs to inverter, output terminal contactor which sets this parameter shall be
CLOSED.
d 2
Frequency arrival. When output frequency of inverter agrees with set frequency, this contactor shall be
CLOSED.
d 3
Zero speed. When inverter set frequency is less than Min starting frequency setting, this contactor shall be
CLOSED.
d 4
Over-torque detection. This contactor shall be CLOSED when over-torque is detected by inverter.
d 5
During external alarm. This contactor shall be CLOSED when external alarm happens to inverter.
d 6
Low voltage detection. This contactor shall be CLOSED when input voltage over-low is detected by inverter.
d 7
External terminal running mode. This contactor shall be CLOSED when inverter reference is controlled by
external terminals.
d 8
Alarm output (for any alarm). This contactor shall be CLOSED when fault is detected by inverter.
d 9
Frequency detection. This contactor shall be CLOSED when output frequency agrees with appointed
reference (3-00).
d 10
During pattern operation. This contactor shall be CLOSED when pattern operation performed.
d 11
Pattern operation one cycle completion. During pattern operation, this contactor shall be CLOSED after
each running step, but it shall maintain only for 0.5sec.
d 12
Pattern operation completion. This contactor shall be CLOSED after completion of pattern operation, but it
shall maintain only for 0.5sec.
d 13
Pattern operation pause. This contactor shall be CLOSED when external pause pattern operation is in
action during program auto running.
d 14
Terminal count value arrival. This contactor shall be CLOSED when count value is equivalent with set value
of Parameter 3-01.
d 15
Terminal designated count value arrival. This contactor shall be CLOSED when count value is equivalent
with set value of Parameter 3-02.
d 16
Inverter ready to run. This contactor shall be CLOSED if no alarm was detected after motor drive power is
supplied.
d 17
Fwd running. When inverter is in fwd run, delay reference time shall be in accordance with setting in
Parameter 3-03, and contactor shall be CLOSED when time met. Relay shall be interrupted when inverter
stops or is switched to Rev run stations. Attention shall be paid that counting here shall begin from Fwd run.
d 18
Rev running. When inverter is in Rev run, delay reference time shall be in accordance with setting in
Parameter 3-04, and contactor shall be CLOSED when time met. Relay shall be interrupted when inverter
stops or is switched to Fwd run stations. Attention shall be paid that counting here shall begin from Rev run.
d 19
Fwd/ Rev running direction. This reference shall be available at switching of Fwd/Rev run. Description of
action: During direction switching of motor drive, the relay shall be Opened and then delayed in a time
complied with setting in 3-03 and 3-04. After delay, the relay shall be closed. Provided that delay setting in
3-03 and 3-04 is 0, relay shall be kept in closed condition and not open until machine stop signal appears.
Notes:
1.“CLOSED” mentioned above refers to closing of normally open contactor(RA-RC), and normally closed contactor
(RB-
RC) shall open simultaneously; while “open” shall refer to opening of normally open contactor(RA-RC), and
normally closed contactor(RB-RC) shall be closed simultaneously.