43
3. OUTPUT FUNCTION PARAMETERS
3-00
Frequency detection(Level)
Factory setting
d 1.0
Setting range
d 1.0<->d 400Hz
Unit
0.1Hz
When output frequency of inverter meets a random appointed frequency value, multifunction external terminal
contactor shall be “Closed” if this terminal is set to d9 (3-05).
3-01
Count value agreement setting
Factory setting
d 0
Setting range
d 0<->d 999
Unit
1
This parameter set the count value of the internal counter of inverter, with one of outside terminals (FWD, REV,
MI3~MI5) as the trigger terminal. When the counting ends (arrives), its appointed signal output the terminal action.
3-02
Appointed count agreement setting
Factory setting
d 0
Setting range
d 0<->d 999
Unit
1
Beginning from ACI, when count value reaches this parameter setting value, the multi-functional corresponding shall
act. This parameter shall be applicable when count is to end. This output signal shall be used prior to machine stop,
to make inverter run in low speed till motor stop.
When the counting value reaches the setting value of 3-01 from ACI, give it one counting pulse again to make it
return to ACI to restart counting. So the setting value of 3-02 must be less than 3-01. When the setting value of 3-02
is more than 3-01, the corresponding multifunction terminals, if any, will not act.
Terminal [RA-RB-RC] Function 3-05=14
Terminal [RA-RB-RC]
Function 3-05=15
Appointed count agreement
3-02=3
3-01=5
Set counting
value reach
(Output signal)
Appointed count agreement
Multi function output
terminal
0-04=1
Width of triggering signal
C0000
C0001
C0005
C0001
C0002
C0003
C0004
C0002
C0000
20msec
Display value
External count
triggering signal
20msec
Set counting value reach
3-03
Fwd run reference delay setting
Factory setting
d 0.0
Setting range
d 0.0<->d 60.0s
Unit
0.1s
3-04
Rev run reference delay setting
Factory setting
d 0.0
Setting range
d 0.0<-> d 60.0s
Unit
0.0s
When 3-05 is set as d17, d18 and d19, above two parameters match with it to use.
3-05
Terminal[RA/B/C] Function(Relay output)
Normally Open Contactor(RA-RC)
Normally Closed Contactor(RB-RC)
Factory setting
d 8
Setting range
d 0<->d 19
Unit
1