47
3-16
Analog input Adjustment for [AVI] (Gain)
Factory setting
d 100%
Setting range
d 0.0%<-> d 100% of Maximum Frequency
Unit
0.1%
These four parameters correspond to the condition when 2-00 or 2-01 is set as d1 (external terminal AVI input DC
0
~
+10V).
3-17
Bias [ACI] (Bias base point)
Factory setting
d 4.0
Setting range
d 0.0<-> d 20.0mA
Unit
0.1mA
3-18
Bias [ACI] (Bias value)
Factory setting
d 0.0%
Setting range
d 0.0%<-> d 100% of Maximum Frequency
Unit
0.1%
3-19
Analog input Adjustment for [ACI] (Gain base point)
Factory setting
d 20.0
Setting range
d 0.0<-> d 20.0mA
Unit
0.1 mA
3-20
Analog input Adjustment for [ACI] (Gain)
Factory setting
d 100%
Setting range
d 0.0%<-> d 100% of Maximum Frequency
Unit
0.1%
These four parameters correspond to the condition when 2-00 or 2-01 is set as d2 (external terminal ACI input DC
4~20mA).
The jumper cap has to switch to current ACI input (4~20mA).
Above eight parameters define the corresponding relationship between analog input voltage and voltage/current.
Output frequency
Analog input
3-13=0.0V
3-17=4.0mA
1-00
3-16
3-20
3-14
3-18
3-13
3-17
3-15
3-19
20mA/10V
Output frequency
Analog input
1-00
3-16=70.0%
3-14=30.0%
3-18=0.0%
3-15=10.0V
3-19=20.0mA
3-20=50.0%
Example:
3-21
Reserved
3-22
Reserved