Definition of address in communications agreement:
Available addresses are listed below
:
Function
Address
Content
AC motor inverter
parameters
ggnnH
gg: indicates parameter group; nn: indicates parameter.
For example: 0401H indicates parameter (4-01). Functions of parameters
shall see descriptions before for reference, when catching parameter by
from command code 03H, only one parameter shall be got for each time.
Command(written
only )
2000H
Bit 0-1
00: Blank
01: Stop reference
10: Run reference
11: JOG+RUN reference
Bit 4-5
00: Blank
01: Fwd reference
10: REV reference
11: Changing direction
Bit 2-3
Bit 6-15
Not used
2001H
Frequency
reference
2002H
Bit 0
1:E.F. ON (External fault)
Bit 1
1:Reset reference
Bit 2
Reserved
2003H
Reserved
Monitor status
(Reference read)
2100H
Error code
00: No alarm records
01: oc ( over current)
02: ov (over voltage)
03: oh (over heating)
04: oL (drive over load)
05: oL1(Motor over load )
06: EF(external fault)
07: CPU writing alarm (cf1)
08: Reserved
09: HPF (Hardware circuit fault)
10: Reserved
11: Reserved
12: Reserved
13: Reserved
14: LV (low voltage)
15: Reserved
16: cF2( CPU read fault)
17: b.b
18: ol2 (over torque)
19: Reserved
20: Reserved