2. Operation mode parameters
Set during running available
Parame
ter
Parameter functions
Setting range
Factory
setting
2-01
Frequency command 2
0:Keys on keypad
1:Input DC 0 to 10V by external terminals AVI
2:Input 4 to 20mA by external terminals ACI
3:controlled by VR on keypad
4:Reserved
5:Reserved
6:Controlled by UP/DOWN
7:Controlled by UP/DOWN(Frequency memory)
8:Reserved
0
2-02
Combination way of frequency
sources
0:Frequency command 1
1:Frequency command 1+Frequency command 2
2:Frequency command 1-Frequency command 2
0
2-03
Operation method
0: Operated by keypad
1: Operated by external terminals. STOP on
keypad available
2: Operated by external terminals. STOP on
keypad unavailable
3: Operated by Communications Interface
RS485. STOP on keypad available
4: Operated by Communications Interface
RS485. STOP on keypad unavailable
0
2-04
Deceleration mode
0: Normal deceleration
1: Coast to stop
0
2-05
Reserved
2-06
External fault (EF) stop mode
0: Reserved
1: External fault (EF) coast to stop
1
2-07
Reference loss detection
(Terminal AVI)( stop mode)
0:Deceleration stop
1:Coast to stop
2:Holding operation command after deceleration
stop
2
2-08
Reserved
2-09
Motor sound(Carrier frequency)
2.0 to 12.0kHz
6.0
2-10
Rotation direction inhibition
0: Fwd/Rev run available
1: Rev run inhibited
2: Fwd run inhibited
0
2-11
Reference loss detection
(Terminal ACI)
( stop mode)
0: Non-processing
1: Coast to stop
2: EF display after deceleration stop
3: Continuous operation by reference frequency
before disconnection
0
2-12
Power on start
0: Operation available
1: Operation unavailable
0
2-13~2-14
Reserved
Parameters marked with “reserved” will be displayed, but will not be used for the inverter. Please do not change the
code of such kind of parameter.