32
Ⅴ
. DESCRIPTION OF FUNCTIONAL PARAMETERS
All the functional parameters are described in detail in this chapter. According to attributes, the parameters can be
divided into 11 groups; in most of the applications, presetting for operation shall be completed by performing with
these parameters of groups.
The 11 groups of parameters are listed as below:
0: User’s Parameters
1: Basic Parameters
2: Operation Mode Parameters
3: Output Function Parameters
4: Input Function Parameters
5: Multi-step and Pattern Operation Parameters
6: Protection Parameters
7: Motor Parameters
8: High Function Parameters
9: Communications Parameters
A : Wobble Frequency Function Parameters
*
: indicates that for 400V class, value shall be 2 times of setting.
: indicates that it’s available to be set during running.
Parameters marked with “reserved” will be displayed, but will not be used for the inverter. Please do not change the
code of such kind of parameter.
0. USER'S PARAMETERS
0-00
Inverter type code recognition (only for reading)
Factory setting
d#
Setting range
Non
Inverter type code shall be read through this parameter, and for capacity of the drive, which has been set at factory,
please see diagram below. Also, it shall be applied to judge whether current in parameter (0-01) corresponds with
rated current of the specific machine. Parameter 0-00 corresponds with 0-01 as the diagram below indicates.
200V(type code)
d1
d2
d3
d4
d5
Power kW
0.2
0.4
0.75
1.5
2.2
Horsepower HP
0.25
0.5
1
2
3
Rated current 0-01(A)
1.6
2.5
4.2
7.5
11.0
400V(type code)
d10
d11
d12
d13
d14
Power kW
0.4
0.75
1.5
2.2
3.7
Horsepower HP
0.5
1
2
3
5
Rated current 0-01(A)
1.5
2.5
4.2
5.5
8.2