7. Motor Parameters
Set during running available
Parame
ter
Parameter functions
Setting range
Factory
setting
7-00
Motor(Rated current)
30 to 120%
85
7-01
Motor(No load current)
0 to 90%
30
7-02
Auto-torque compensation setting
0.0 to 30.0
0.0
7-03
Auto slip compensation setting
0.0 to 10.0
0.0
7-04~7-10
Reserved
7-11
Motor(Rated speed)
500 to 3000min
-1
1450
7-12
Motor(Pole number)
0 to 30pole
4
7-13
Motor(Rated frequency)
5.0 to 400Hz
50.0
7-14~7-74
Reserved
Parameters marked with “reserved” will be displayed, but will not be used for the inverter. Please do not change the
code of such kind of parameter.
8. High Function Parameters
Set during running available
Parame
ter
Parameter functions
Setting range
Factory
setting
8-00
DC braking(Braking level)
0.0 to 100%
0.0
8-01
DC braking(Braking time setting at
starting)
0.0 to 60.0S
0.0
8-02
DC braking(Braking time setting at
stopping)
0.0 to 60.0S
0.0
8-03
DC braking(Braking starting
frequency)
0.1 to 60.0Hz
1.0
8-04
Restart after momentary power
failure (Mode selection)
0:Inactive(Trip immediately)
1:Active(Restart at the frequency at which the
power failure occurred, for general loads)
2:Active(Restart at the starting frequency, for
light inertia loads)
0
8-05
Max allowable time for power failure
0.3 to 5.0s
2.0
8-06
Restart time
0.3 to 5.0s
0.5
8-07
Max current setting for speed
tracking
30 to 200%
150
8-08
Jump frequency 1(Upper)
0.0 to 400Hz
0.0
8-09
Jump frequency 1(Lower)
0.0 to 400Hz
0.0
8-10
Jump frequency 2(Upper)
0.0 to 400Hz
0.0
8-11
Jump frequency 2(Lower)
0.0 to 400Hz
0.0
8-12
Jump frequency 3(Upper)
0.0 to 400Hz
0.0
8-13
Jump frequency 3(Lower)
0.0 to 400Hz
0.0
8-14
Auto-reset(Times)
0 to 10
0
8-15
AVR function selection
0:AVR function available
1:AVR function unavailable
2:AVR function cancelled during deceleration
1
8-16
Reserved
8-17
Reserved
8-18
Reserved