PROGRAMMING GUIDE
SINUS PENTA
89
/
486
Table 21: Preset PID units of measure
Unit of
Measure
P267/P267b
Item
Displayed
Unit of
measure
P267/P267b
Item
Displayed
Customized
0: Disabled
----(see
P267a
)
m
18: m
m
bar
1: bar
bar
ft
19: ft
ft
mbar
2: mbar
mbar
m/s
20: m/s
m/s
atm
3:atm
atm
ft/s
21: ft/s
ft/s
Pa
4: Pa
Pa
rpm
22: rpm
rpm
kPa
5: kPa
kPa
gal/s
23: GPS
GPS
PSI
6: PSI
PSI
gal/min
24: GPM
GPM
m
3
/s
7: m3/s
m3/s
gal/h
25: GPH
GPH
m
3
/min
8: m3/m
m3/m
ft
3
/s
26: CFS
CFS
m
3
/h
9: m3/h
m3/h
ft
3
/min
27: CFM
CFM
l/s
10: l/s
l/s
ft
3
/h
28: CFH
CFH
l/min
11: l/m
l/m
A
29: A
A
l/h
12: l/h
l/h
V
30: V
V
°
13: °
°
W
31: W
W
°C
14: °C
°C
kW
32: kW
kW
°F
15: °F
°F
HP
33: HP
HP
Nm
16: Nm
Nm
CV
34: CV
CV
kgm
17: kgm
kgm
P267a/P267c Custom PID/PID2 Units of Measure
P267a
Range
0x20
÷
0x8A (every byte)
ASCII 0x20 = blank
ASCII 0x8A =
Default
0x015D255B
ASCII 0x5D = [
ASCII 0x25 = %
ASCII 0x5B = ]
⇒
[%]
Level
ENGINEERING
Address
1867/1869
(This is a 32-bit data item)
Characters are 8-bit ASCII encoded; there are three 8-
bit characters starting from the least significant bit. Bit
24 must always be set to 1.
Function
Parameter
P267a/P267c
is active only if
P267/P267b
= 0: [Disable] and it relates to
the unit of measure actually displayed in
M023
,
M024, M023a
,
M024a
. This
parameter allows setting a 3-character string to display the units of measures for the
PID Measures:
M023
,
M024, M023a
,
M024a
.
Press the
SAVE/ENTER
key to edit each character: when a flashing cursor appears
on the left of each character, press
▲
and
▼
to scroll all the characters displayed.
Press the
ESC
key to go to the next character. Press
SAVE/ENTER
to store the new
parameter value.
NOTE
See also parameter
P257/P457