SINUS PENTA
PROGRAMMING GUIDE
418
/
486
49. TIMED
FLAGS
MENU
49.1.
Overview
The Timed Flag Menu includes the parameters setting the four timed flags for the inverter, TFL1..4. The following data
items are set for each timed flag: activation time (Time ON), deactivation time (Time OFF), days of the week when
activation shall occur.
The timed flags may be used as they were digital inputs, both when managing digital outputs (MDO) and when
managing virtual digital outputs (MPL). It is also possible to assign the same control functions that can be associated to
the other digital inputs (see DIGITAL INPUTS MENU).
NOTE
The Timed Flags Menu may be accessed only if the Data Logger board is installed (even the
ES851 RTC version only) and if parameter
R021
Data Logger setting is set to 2: ENABLE.
49.2.
Examples
Every time flag features 3 parameters (Hour, Minute, Second) setting the activation time of the flag itself; 3 parameters
(Hour, Minute, Second) setting the deactivation time of the flag itself; 1 parameter setting the days of the week when the
flag shall activate. If the activation time precedes the deactivation time, the flag will have the TRUE logic value at the
activation time, whilst it will have the FALSE logic value at the deactivation time in the days of the week concerned. If
the activation time is subsequent to the deactivation time, the flag will have the TRUE logic value at the activation time,
whilst it will have the FALSE logic value at the deactivation time of the following day.
Example 1:
C330
TFL1: Time ON – Hour
08
C331
TFL1: Time ON – Minutes
00
C332
TFL1: Time ON – Seconds
00
C333
TFL1: Time OFF – Hour
20
C334
TFL1: Time OFF – Minutes
00
C335
TFL1: Time OFF – Seconds
00
C336
TFL1: Days of the week
1000000
The timed flag TFL1 is TRUE from 8:00:00AM to 08:00:00PM every Monday.
Example 2:
C330
TFL1: Time ON – Hour
20
C331
TFL1: Time ON – Minutes
00
C332
TFL1: Time ON – Seconds
00
C333
TFL1: Time OFF – Hour
08
C334
TFL1: Time OFF – Minutes
00
C335
TFL1: Time OFF – Seconds
00
C336
TFL1: Days of the week
1000000
The timed flag TFL1 is TRUE from 08:00:00PM on every Monday to 8:00:00AM on every Tuesday.