PROGRAMMING GUIDE
156/486
P176 AO1Analog Output
P176
Range
0
÷
7
0: Disabled,
1: ± 10V,
2: 0 ÷ 10V,
3: 0 ÷ 20mA,
4: 4 ÷ 20mA,
5: ABS 0 ÷ 10V,
6: ABS 0 ÷ 20mA,
7: ABS 4 ÷ 20mA.
Default
1
1: ± 10V
Level
ADVANCED
Address
776
Function
Selects the operating mode of AO1analog output.
P 1 7 6 T y p e o f
O u t p u t S i g n a l
A O 1
S W 2 - 1 - 2
→
0 - 2 0 m A
In the example above, A01 is set as a current input. Contact 1 of SW2 dip-switch is open, contact 2 is closed.
NOTE
Analog outputs are set as voltage outputs by default. To set them as current outputs, see
the DIP-switch configuration and follow the instructions displayed on the keypad, or refer to
the Sinus Penta’s Installation Guide.
P177 Selected Variable for AO1 Analog Output
P177
Range
0
÷
69
Default
1
Motor speed
Level
ADVANCED
Address
777
Function
Selects the variable to be allocated to AO1 digital output.
P178 Min. value of AO1 Selected Variable
P178
Range
-32000 ÷ +32000
Depending on the value selected
in
P177
- 320.00% ÷ + 320.00 % of the full-scale
value
See Table 36
Default
–1500
–15.00% of 10000 rpm = –1500 rpm
Level
ADVANCED
Address
778
Function
Minimum value of the variable selected via
P177,
corresponding to the min.
output value of AO1 set in
P182.