41. POWER
DOWN
MENU
41.1.
Overview
In the case of power failure, the drive can be kept powered on by exploiting the kinetic energy of the motor and the load:
energy recovered due to motor slowing down is used to power the drive, thus avoiding losing the drive control when a
black–out occurs.
All parameters relating to the Power Down function are included in the Power Down submenu in the Configuration
menu.
The following options are available (parameter
C225
):
– [
NO
]: The function is disabled.
– [
YES
]: After the time set in
C226
(Power Down start delay), starting from the instant when power down occurs, a
deceleration ramp takes place (deceleration ramp in Power Down
C227
). The time period of the deceleration ramp can
be user-defined.
– [
YES V
]: In case of power down for a time longer than
C226
, the motor coasts to stop, so that DC bus voltage value is
kept constant at
C230
. To do so, a PI (proportional–integral) regulator is used, which is adjusted through parameter
C231
(proportional term) and
C232
(integral term).
– [
Alarm
]: In case of power down, when the time set in
C226
is over, alarm
A064
trips
(factory setting).
NOTE
If the mains loss deactivates the
ENABLE-A
and
ENABLE-B
commands, the motor cannot
coast to stop, because these commands are required for the hardware enable of IGBTs.
NOTE
If a drive is DC-powered by a Regenerative Penta (or an equivalent drive stabilizing DC bus
voltage), Power Down cannot occur (
C008
= xT Regen, where x can be 2, 4, 5, or 6 ).
Figure 63: Power Down (Example)