PROGRAMMING GUIDE
SINUS PENTA
219
/
486
P312 XMDO4: Signal Selection
P312
Range
0
÷
79
Default
0
D0: Disable
Level
ENGINEERING
Address
912
Function
Selects the digital signal used to calculate the value of
XMDO4
digital output.
It selects an analog variable used to calculate the value of
XMDO4
digital input if
one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 48.
P313 XMDO4: Output Logic Level
P313
Range
0–1
0: TRUE
1: FALSE
Default
1
1: FALSE
Level
ENGINEERING
Address
913
Function
XMDO4
digital output logic function to apply a logic reversal (negation) to the
calculated output signal: (0) FALSE = a logic negation is applied; (1) TRUE = no
negation is applied.
P314 XMDO5: Signal Selection
P314
Range
0
÷
79
Default
0
D0: Disable
Level
ENGINEERING
Address
914
Function
Selects the digital signal used to calculate the value of
XMDO5
digital output.
It selects an analog variable used to calculate the value of
XMDO5
digital input if
one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 48.
P315 XMDO5: Output Logic Level
P315
Range
0–1
0: FALSE
1: TRUE
Default
1
1: TRUE
Level
ENGINEERING
Address
915
Function
XMDO5
digital output logic function to apply a logic reversal (negation) to the
calculated output signal: (0) FALSE = a logic negation is applied; (1) TRUE = no
negation is applied.