SINUS PENTA
PROGRAMMING GUIDE
430
/
486
52.2.
List of Parameters R016 to R018b and I080
Table 128: List of parameters R016 to R018b and I080
Parameter
FUNCTION
User
Level
MODBUS
Address
Default
Values
R016
Fieldbus Watchdog Time
ENGINEERING
603
0 ms
R017
Analog Outputs Controlled by the Fieldbus
ENGINEERING
604
000b
R018
Node Address in the Fieldbus
ENGINEERING
230 bit 0-7
0
R018a
Fieldbus BaudRate
ENGINEERING
230 bit 8-11
125k
R018b
Type of Fieldbus Watchdog
ENGINEERING
230 bit 12-
15
0
→
bit
15 at 1
I080
IP Address Reset
ENGINEERING
519
Inactive
R016 Fieldbus Watchdog Time
R016
Range
0
÷
60000
0
÷
60000 ms
Default
0
0 ms
Level
ENGINEERING
Address
603
Function
If not set to zero, this parameter determines the time limit after which
A070
Fieldbus
WDG trips if no legal writing is received from the fieldbus
.
NOTE
The Watchdog activates only once the drive has received the first legal message from the
master, as described in Alarm A070 (Communication Suspended). This avoids untimely
activation due to different start times between the master and the drive.
R017 Analog Outputs Controlled by the Fieldbus
R017
Range
000b
÷
111b binary
0000h
÷
0007h hex
0
÷
7 decimal
000b
→
None
001b
→
AO1
010b
→
AO2
100b
→
AO3
Default
000b
000b
→
None
Level
ENGINEERING
Address
604
Function
To select analog outputs controlled by the fieldbus, select the bit corresponding to
the analog output to be controlled.
Example:
R017
= 0011b = 3 decimal
→
analog outputs AO1 and AO2 are controlled directly
by the fieldbus,
irrespective
R018 Node Address in the Fieldbus
R018
Range
0
÷
126 for Profibus
0
÷
63 for DeviceNet
0
÷
126 for Profibus
0
÷
63 for DeviceNet
Default
0
0
Level
ENGINEERING
Validity
Boards: B40
Profibus and DeviceNet
Address
230 bit 0-7
Function
This is the slave address.
This parameter is active only for Profibus and DeviceNet fieldbus with B40 boards.