PROGRAMMING GUIDE
SINUS PENTA
363
/
486
40. DC
BRAKING
MENU
40.1.
Overview
When the IFD or VTC control algorithm are used, DC current can be injected into the motor to stop it. DC current may
be automatically injected at stop and/or at start; DC current injection may also be controlled by the terminal board. All
relevant parameters are included in the DC BRAKING MENU. The intensity of the DC current injected is expressed as a
percentage of the rated current of the active motor.
40.1.1.
DC
B
RAKING AT
S
T ART AND
N
ON
-
CONDENSING
F
UNCT ION
To activate DC braking at start, set
C216
to [YES]. Braking occurs after sending a
START
command, with a speed
reference other than zero, before the acceleration ramp. A
START
command may be one of the following:
RUN
command or
REV
command sent via terminal board;
START
command from keypad, etc., depending on the preset
control mode. DC braking level and duration are set in the following parameters:
C220
Expressed as a percentage of the rated current of the controlled motor.
C218
Expressed in seconds.
Figure 57: DCB Hold and DCB at Start
Output speed, holding and DC braking current when the DCB Hold and DCB at Start functions are active.