PROGRAMMING GUIDE
SINUS PENTA
331/486
The figure below illustrates the processing logic diagram for the
START
,
REV, Cw/CCw
functions and the
START,
STOP, REV
keys
on the display/keypad, if the
STOP
function is programmed.
Figure 54: Controlling Run and Direction when the STOP Input is programmed
C152 ENABLE-SW Input
C152
Range
0
÷
16
0
÷
24 if ES847 or ES870 if fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1152
Function
This is an additional software-controlled Enable signal which is estimated in
series to the
ENABLE
function associated to
MDI2
inputs. If this function is
enabled, the drive is enabled
if and only if
the
ENABLE-A
,
ENABLE-B
and
ENABLE-SW
inputs are simultaneously activated.
If the
ENABLE-SW
function is programmed (
C152
≠
0), do the following to
enable the drive:
•
activate the
ENABLE-SW
signal
•
activate the
ENABLE-A
and
ENABLE-B
signals
•
activate
MDI2
inputs via serial link and fieldbus, if those inputs are
selected via
C140
,
C141
,
C142
.
•
activate the
DISABLE
signal if programmed via
C153.
NOTE
The
ENABLE-SW
signal may not delayed by the timers: if a timer is programmed to the
terminal related to the
ENABLE-SW
signal, this will not affect the
ENABLE-SW
function,
while it normally delays other functions set to the same terminal.