PROGRAMMING GUIDE
SINUS PENTA
253
/
486
P394 Filtering Time over XAIN4 Input
P394
Range
0
÷
+65000
0
÷
+65000ms
Default
100
100 ms
Level
ADVANCED
Address
994
Function
This parameter selects the value of the filter time constant of the first command
applied to the XAIN4 input signal when the signal saturation and conversion is
over.
P395 Type of Signal over XAIN5 Input
P395
Range
2
÷
4
2:
±
20 mA
3: 4
÷
20 mA
4: 0
÷
20 mA
Default
3
3: 4
÷
20 mA
Level
ADVANCED
Address
995
Function
This parameter selects the type of differential analog signal over terminals
X
AIN5+
and X
AIN5–
in the terminal board.
The signal can be a current signal, a unipolar signal, or a bipolar signal.
2:
±
20 mA Bipolar current input between –20mA and +20mA. The detected signal
is saturated between these two values.
3
: 4
÷
20 mA Unipolar current input with min. threshold, b4 mA and
+20mA. The detected signal is saturated between these two values.
Before being saturated, if the detected signal is lower than 4 mA or greater than
20 mA, alarms
A069
or
A086
trip.
4
: 0
÷
20 mA Unipolar current input b0 mA and +20mA. The detected
signal is saturated between these two values.
P396 Value of XAIN5 Producing Min. Reference (X-axis
P396
Range
–200
÷
200, if
P395
= 2
+40
÷
200, if
P395
= 3
0
÷
200, if
P395
= 4
–20.0 mA
÷
20.0 mA, if
P395
= 2:
±
20 mA
+4.0mA
÷
20.0 mA, if
P395
= 3: 4
÷
20 mA
0.0 mA
÷
20.0 mA, if
P395
= 4: 0
÷
20 mA
Default
40
+4.0mA
Level
ADVANCED
Address
996
Function
This parameter selects the value for XAIN5 input signal for minimum reference, or
better the reference set in
C028xP396a
(Master mode) or in
C047xP396a
(Slave
mode). If motor 2 is active,
C071
and
C090
will be used instead of
C028
and
C047
; if motor 3 is active, the values set in
C114
and
C133
will be used.
P396a Percentage of Speed_Min/Trq_Min Producing Min. Reference (Y-axis related to P396)
P396a
Range
0
÷
1000
100.0%
Default
1000
100.0%
Level
ADVANCED
Address
711
Function
This parameter represents the min. speed percentage (or the min. torque
percentage for a torque reference) to be used for the minimum reference set with
P396.