C169 JOG Input
C169
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1169
Function
When the JOG function is enabled, the motor rotates at low speed following slow
ramps which are manually controlled by the user only by means of the keys in keypad.
If the drive is enabled (
ENABLE
function activated) but is not running, and if the JOG
terminal is enabled, the drive will run: the connected motor will accelerate following a
JOG ramp (
P029
) up to the JOG speed reference (
P070
). On the other hand, if the
terminal is disabled, the drive will stop: the connected motor will decelerate to zero
speed following the JOG ramp (
P029
).
Reverse the direction of rotation of the active reference to reverse the
JOG
reference.
CAUTION
The motor starts running as soon as this terminal is activated (only if the drive is
enabled).
NOTE
The
RUN
function will override the
JOG
function.
Therefore, if the
RUN
function is active, the
JOG
function is ignored.
NOTE
If the motor is not running in
SLAVE mode
(torque reference instead of speed
reference), it can rotate at JOG speed when the user activates the
JOG
function.
In
SLAVE mode
, the
JOG
function is ignored if the motor is still rotating due to an
active reference torque.
C169a Input for Selection of Speed Regulator Parameters
C169a
Range
0
÷
16
0
÷
24 if ES847 or ES870 is fitted
0
→
Inactive
1
÷
8
→
MDI1
÷
MDI8
9
÷
12
→
MPL1
÷
MPL4
13
÷
16
→
TFL1
÷
TFL4
17
÷
24
→
XMDI1
÷
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1233
Control
FOC
Function
This function allows switching between the two parameter sets pertaining to the
speed regulator.
The two pairs of parameters concerned are the same as the parameters
activating in case of automatic regulation based on the speed error (see
SPEED LOOP AND CURRENT BALANCING MENU).
For example, parameters
P126/P128
and
P125/P129
apply to
Motor 1
.
Always referring to
Motor 1
, a low logic level of the input associated to the
selector keeps parameters
P126/P128
active, while a high logic level affects
speed regulation via parameters
P125/P129
.
This applies to Motor 2 and Motor 3 as well for parameters
P136/P138
and
P135/P139
for
Motor 2
, or
P146/P148
and
P145/P149
for
Motor 3
.