SINUS PENTA
PROGRAMMING GUIDE
322
/
486
Figure 52: The ENABLE Function
NOTE
If the STO function is to be adopted, the control mode and the control circuit of the
ENABLE-
A
and
ENABLE-B
signals must be accomplished as per the Safe Torque Off Function -
That manual also includes a detailed validation procedure of the control configuration of the
STO function to be executed upon first start-up and also periodically at yearly intervals.
If the
ENABLE
input is disabled, the drive output voltage is always set to zero, so the connected motor starts
idling
(the
motor idles and stops due to friction or the mechanical load).