SINUS PENTA
PROGRAMMING GUIDE
252
/
486
P391 Value of XAIN4 Input Producing Min. Reference
P391
Range
–100
÷
100, if
P390
= 0
0
÷
100, if
P390
= 1
–10.0 V
÷
10.0 V, if
P390 =
0:
±
10 V
0.0 V
÷
10.0V, if
P390
= 1: 0
÷
10 V
Default
0
0.0V
Level
ADVANCED
Address
991
Function
This parameter selects the value for XAIN4 input signal for minimum reference,
or better the reference set in
C028 xP391a
(Master mode) or in
C047xP391a
(Slave mode). If motor 2 is active,
C071
and
C090
will be used instead of
C028
and
C047
; if motor 3 is active, the values set in
C114
and
C133
will be used.
P391a Percentage of Speed_Min/Trq_Min. Producing Min. Reference (Y-axis related to P391)
P391a
Range
0
÷
1000
100.0%
Default
1000
100.0%
Level
ADVANCED
Address
704
Function
This parameter represents the min. speed percentage (or the min. torque
percentage for a torque reference) to be used for the minimum reference set with
P391.
P392 Value of XAIN4 Input Producing Max. Reference (X-axis)
P392
Range
–100
÷
100, if
P390
= 0
0
÷
100, if
P390
= 3
–10.0 V
÷
10.0 V, if
P390 =
0:
±
10 V
0.0 V
÷
10.0V, if
P390
= 1: 0
÷
10 V
Default
100
+10.0V
Level
ADVANCED
Address
992
Function
This parameter selects the value for XAIN4 input signal for maximum reference, or
better the reference set in
C029xP392a
(Master mode) or in
C048xP392a
(Slave
mode). If motor 2 is active,
C072
and
C091
will be used instead of
C029
and
C048
; if motor 3 is active, the values set in
C115
and
C134
will be used.
P392a Percentage of Speed_Max/Trq_Max Producing Max. Reference (Y-axis related to P392)
P392a
Range
0
÷
1000
100.0%
Default
1000
100.0%
Level
ADVANCED
Address
710
Function
This parameter represents the max. speed percentage (or the max. torque
percentage for a torque reference) to be used for the maximum reference set
with
P392.
P393 Offset over XAIN4 Input
P393
Range
–1000
÷
1000
–10.00 V
÷
+10.00 V
Default
0
0.00 V
Level
ADVANCED
Address
993
Function
This parameter selects the offset correction value of the XAIN4 analog signal that
has been measured.
The value set is added to the signal measured before saturation or conversion; its
unit of measure is the same as the one of the signal selected for XAIN4 analog
input.