SINUS PENTA
PROGRAMMING GUIDE
72
/
486
8.10.
Encoder Measures Menu
The Encoder Measures Menu displays the measures of the incremental and absolute position sensors (if any), as well
as some useful info for managing those sensors.
M120 Encoder A Count Value
M120
Range
0
÷
65535
0
÷
65535
Note: The actual range of this measure is based on the type of
encoder being used.
Active
Always active
Address
1743
Function
This is the count value of encoder A (see ENCODER/FREQUENCY INPUTS MENU).
When the inverter is powered on, the initial value is always 0.
M121 Encoder B Count Value
M121
Range
0
÷
65535
0
÷
65535
Note: The actual range of this measure is based on the type of
encoder being used.
Active
Always active
Address
1744
Function
This is the count value of encoder B (see ENCODER/FREQUENCY INPUTS MENU).
When the inverter is powered on, the initial value is always 0.
M122 Absolute Encoder Count Value
M122
Range
0
÷
65535
0
÷
65535
Note: The actual range of this measure is based on the type of
encoder being used.
Active
Always active
Address
1747
Function
This is the count value of the absolute encoder (or encoder M) (see
ENCODER/FREQUENCY INPUTS MENU).
When the inverter is powered on, the initial value is always 0.