SINUS PENTA
PROGRAMMING GUIDE
112
/
486
13.3.
List of Parameters P050 to P074a
Table 27: List of parameters P050 to P074a
Parameter
FUNCTION
User Level
DEFAULT
VALUE
MODBUS
Address
P050
Type of signal over
REF
input
ADVANCED
3: 0
÷
10V
650
P051
Value of
REF
input producing min. reference (X-axis)
ADVANCED
0.0V
651
P051a
Percentage of Speed_Min/Trq_Min producing min.
reference (Y-axis related to
P051
)
ADVANCED
100.0%
675
P052
Value of
REF
input producing max. reference (X-axis)
ADVANCED
10.0V
652
P052a
Percentage of Speed_Max/Trq_Max producing max.
reference (Y-axis related to
P052
)
ADVANCED
100.0%
676
P053
Offset over
REF
input
ADVANCED
0V
653
P054
Filtering time over
REF
input
ADVANCED
5 ms
654
P055
Type of signal over
AIN1
input
ADVANCED
2: 4
÷
20mA
655
P056
Value of
AIN1
input producing min. reference (X-axis)
ADVANCED
4.0mA
656
P056a
Percentage of Speed_Min/Trq_Min producing min.
reference (Y-axis related to
P056
)
ADVANCED
100.0%
677
P057
Value of
AIN1
input producing max. reference (X-axis)
ADVANCED
20.0mA
657
P057a
Percentage of Speed_Max/Trq_Max producing max.
reference (Y-axis related to
P057
)
ADVANCED
100.0%
678
P058
Offset over
AIN1
input
ADVANCED
0mA
658
P059
Filtering time over
AIN1
input
ADVANCED
5 ms
659
P060
Type of signal over
AIN2
input
ADVANCED
2: 4
÷
20mA
660
P061
Value of
AIN2
input producing min. reference (X-axis)
ADVANCED
4.0mA
661
P061a
Percentage of Speed_Min/Trq_Min producing min.
reference (Y-axis related to
P061
)
ADVANCED
100.0%
679
P062
Value of
AIN2
input producing max. reference (X-axis)
ADVANCED
20.0mA
662
P062a
Percentage of Speed_Max/Trq_Max producing max.
reference (Y-axis related to
P062
)
ADVANCED
100.0%
701
P063
Offset over
AIN2
input
ADVANCED
0mA
663
P064
Filtering time over
AIN2
input
ADVANCED
5 ms
664
P065
Minimum reference and
START
disabling threshold
ADVANCED
0
665
P066
START
disable delay at
P065
threshold
ADVANCED
0s
666
P067
Keypad and terminal board UP/DOWN ramp
ADVANCED
Quadratic
667
P068
Storage of UP/DOWN values at Power Off
ADVANCED
YES
668
P068a
Reset UP/DOWN speed/torque at Stop
ADVANCED
0:[NO]
940
P068b
Reset UP/DOWN PID at Stop
ADVANCED
0:[NO]
941
P068c
Reset UP/DOWN speed/torque at Source Changeover
ADVANCED
0:[NO]
942
P068d
Reset UP/DOWN PID at Source Changeover
ADVANCED
0:[NO]
943
P069
Range of UP/DOWN reference
ADVANCED
1: Unipolar
669
P070
Jog reference (speed/torque)
ADVANCED
0%
670
P071
Value of
FIN
producing min. reference (X-axis)
ADVANCED
10 kHz
671
P071a
Percentage of Speed_Min/Trq_Min producing min.
reference (Y-axis related to
P071
)
ADVANCED
100.0%
713
P072
Value of
FIN
producing max. reference (X-axis)
ADVANCED
100 kHz
672
P072a
Percentage of Speed_Max/Trq_Max producing max.
reference (Y-axis related to
P072
)
ADVANCED
100.0%
714
P073
Value of
ECH
producing min. reference (X-axis)
ADVANCED
0 rpm
673
P073a
Percentage of Speed_Min/Trq_Min producing min.
reference (Y-axis related to
P073
)
ADVANCED
100.0%
702
P074
Value of
ECH
producing max. reference (X-axis)
ADVANCED
+1500 rpm
674
P074a
Percentage of Speed_Max/Trq_Max producing max.
reference (Y-axis related to
P074
)
ADVANCED
100.0%
703
Содержание PENTA MARINE
Страница 173: ...PROGRAMMING GUIDE SINUS PENTA 173 486 Figure 27 Response to the step based on the value of Kp when Ti is kept constant...
Страница 196: ...SINUS PENTA PROGRAMMING GUIDE 196 486 Figure 34 ANALOG Mode Figure 35 DOUBLE DIGITAL Mode...
Страница 197: ...PROGRAMMING GUIDE SINUS PENTA 197 486 Figure 36 General structure of the parameterization of a digital output...