SINUS PENTA
PROGRAMMING GUIDE
242
/
486
P366 MPL2: Function Applied to the Result of the 2 Tests
P366
Range
0
÷
12
0: (A) OR (B)
1: (A) SET (B) RESET
2: (A) AND (B)
3: (A) XOR (B)
4: (A) NOR (B)
5: (A) NAND (B)
6: (A\) OR (B)
7: (A) OR (B\)
8: (A\) AND (B)
9: (A) AND (B\)
10: (A) RESET (B) SET RISING EDGE
11: (A) SET (B) RESET FALLING EDGE
12: (A) RESET (B) SET FALLING EDGE
Default
1
1: (A) SET (B) RESET
Level
ADVANCED
Address
966
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value.
P366a MPL2: Selecting Variable C
P366a
Range
0
÷
79
Default
0
D0: Disable
Level
ADVANCED
Address
934
Function
This parameter selects the digital signal used to calculate the value of
MPL2
digital output.
The digital signals that can be selected are given in Table 48.
P366b MPL2: Function Applied to the Result of f(A,B) C
P366b
Range
0
÷
12
0: f(A,B) OR (C)
1: f(A,B) SET (C) RESET RISING EDGE
2: f(A,B) AND (C)
3: f(A,B) XOR (C)
4: f(A,B) NOR (C)
5: f(A,B) NAND (C)
6: (A\) OR (B)
7: (A) OR (B\)
8: (A\) AND (B)
9: (A) AND (B\)
10: (A) RESET (B) SET RISING EDGE
11: (A) SET (B) RESET FALLING EDGE
12: (A) RESET (B) SET FALLING EDGE
Default
0
0: f(A,B) OR (C)
Level
ADVANCED
Address
935
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value.