RFL 9508 PLC-TT
RFL Electronics Inc.
September 5, 2012
3
(973) 334-3100
SPECIFICATIONS
As of the date this Instruction Data Sheet was published, the following specifications apply to the RFL
PLC-TT module. Because all RFL products undergo constant refinement and improvement, these
specifications are subject to change without notice.
ENVIRONMENTAL
ANSI C37.90 – 1989:
(service conditions)
Operating temperature:
- 20oC to + 65oC
Storage temperature:
- 40oC to + 75oC
Humidity:
95% @ 40oC non-condensing
SWC/ FAST TRANSIENT
ANSI
C37.90:
(dielectric)
ANSI C37.90.1:
(SWC & fast transient)
RFI SUSCEPTIBILITY
ANSI C37.90.2
35 V/M
OPTICAL INPUT SPECIFICATIONS
Operating voltage range
48 Vdc:
38-60 Vdc
125 Vdc:
88-150 Vdc
250 Vdc:
200-280 Vdc
Input threshold:
1/2 nominal station battery
SOLID STATE OUTPUT SPECIFICATIONS
Maximum continuous output current: 1 Amp
Maximum surge current (100 ms):
10 Amps
Minimum output current:
20 ma
Maximum open circuit voltage:
280 Vdc
OPTIONAL RELAY OUTPUTS
Maximum continuous current:
2 A (inductive)
Maximum surge current (100 ms):
30 A
Maximum breaking current:
1 A resistive
Maximum open circuit voltage:
280 Vdc
Maximum operate time:
5 ms