RFL 9508 PLC-TT
RFL Electronics Inc.
September 5, 2012
16
(973) 334-3100
Table 4. PLC-TT Card Settings
Description
Value
Notes
Output 1 Triphold Timer
Output 2 Triphold Timer
Output 3 Triphold Timer
Output 4 Triphold Timer
0.25-63.75ms
In 0.25ms steps
Output 1 Pretrip Timer
Output 2 Pretrip Timer
Output 3 Pretrip Timer
Output 4 Pretrip Timer
0-3.75ms
In 0.25ms steps
Output 1 Polarity
Output 2 Polarity
Output 3 Polarity
Output 4 Polarity
Inverted/Not Inverted
Output 1 Unblock Enable
Output 2 Unblock Enable
Output 3 Unblock Enable
Output 4 Unblock Enable
Enable/Disable
Shelf Alert Extension
Alarm Time Delay
0ms-2550ms
In 10ms steps
Bus Direction
Terminal D&I-A/D&I-B
Timeslot
1-24 for T1
1-31 for E1
Read
Standard Status/ Trip Input Counters/ or Trip
Output Counters
Input Type 1
Input Type 2
Input Type 3
Input Type 4
OR’ed/AND’ed
Boost
Boost/No Boost
Mode
2+2 mode/3+1 mode
Reset Counter
Enable Counters/ Reset Counters
Output Enable
Enable/Disable
Input 1 Polarity
Input 2 Polarity
Input 3 Polarity
Input 4 Polarity
Inverted/Not Inverted
Aux Input 1 Polarity
Aux Input 2 Polarity
Aux Input 3 Polarity
Aux Input 4 Polarity
Inverted/Not Inverted