![RFL Electronics 9508D UCC Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/rfl-electronics/9508d-ucc/9508d-ucc_instruction-manual_1450369125.webp)
Configuration
5.3.2.10
5.3.2.11
5.3.3
‘50W’ SYSTEMS
50Watt systems require jumpers to be set on the Balance Board as follows:
J2 must be set to the 1-2 position.
J3 must be set to the 2-3 position.
J4 must be set to the 2-3 position.
Refer to paragraph 5.3.2.3 and Figure 7-9 for the location of these jumpers.
‘100W’ SYSTEMS
100Watt systems require jumpers to be set on the Balance Board as follows:
J2 must be set to the 2-3 position.
J3 must be set to the 1-2 position.
J4 must be set to the 1-2 position.
Refer to paragraph 5.3.2.3 and Figure 7-9 for the location of these jumpers.
CHANGING THE RF FREQUENCY BAND
The RFL9508D is typically shipped from the factory preprogrammed for the desired RF frequency
band. In the event that the user wishes to change the operating band The following steps must be
taken.
Tune the TX filter to the proper band (section 5.3.2.2)
Tune the RX filter to the proper band (section 5.3.2.6)
Set the transceiver Transmit and receive frequencies (section 4.5.3.10)
Perform the commissioning procedure (section 6)
RFL 9508D UCC
RFL Electronics Inc.
May 27, 2011
5-45
(973) 334-3100