AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 366 of 485
Query Format
SYSTem:AIO:INput[n]:OFFSET:DEFault?
Description
Returns the default offset for the specified analog input.
Parameters
None
Returned Data Format
n/a
Query Example
SYST:AIO:IN1:OFFSET:DEF?
15.0
Query Format
SYSTem:AIO:INput[n]:OFFSET:MAXimum?
Description
Returns the maximum offset for the specified analog input.
Parameters
None
Returned Data Format
n/a
Query Example
SYST:AIO:IN1:OFFSET:MAX?
100000.000000
Query Format
SYSTem:AIO:INput[n]:OFFSET:MINimum?
Description
Returns the minimum offset for the specified analog input.
Parameters
None
Returned Data Format
n/a
Query Example
SYST:AIO:IN1:OFFSET:MIN?
-100000.000000
Command Syntax
SYSTem:AIO:INput[n]:RANGe <nr2>
Description
Sets the range of the specified analog input.
Available range is 0.0 ~ 10.
Parameters
Offset
Parameter Format
<nr2>
Example
SYST:AIO:IN1:RANG 50.0
Query Format
SYSTem:AIO:INput[n]:RANGe?
Returned Data Format
<nr2>
Query Example
SYST:AIO:IN1:RANG?
10.00
Query Format
SYSTem:AIO:INput[n]:RANGe:DEFault?
Description
Returns the default range for the specified analog input.
Parameters
None
Returned Data Format
n/a
Query Example
SYST:AIO:IN1:RANG:DEF?
0.0
Query Format
SYSTem:AIO:INput[n]:RANGe:MAXimum?
Description
Returns the maximum range for the specified analog input.
Parameters
None
Returned Data Format
n/a
Query Example
SYST:AIO:IN1:RANG:MAX?
10.0
Содержание AFX Series