< 5 Vdc Line to Gnd
CHECK ALL THREE INPUT
LINES POSITIONS
Consult the table below for recommended wire size by model number and AC input rating.
MODEL
INPUT VOLTAGE
INPUT CURRENT
RECOMMENDED
INPUT SERVICE
MINIMUM COPPER WIRE
SIZE, 75°C RATED
390AFX-2
208 V ac, 3~
37 A rms, max
40 A rms
10 mm^2 (AWG 8)
3120AFX-2
208 V ac, 3~
48 A rms, max
50 A rms
10 mm^2 (AWG 8)
3150AFX-2
208 V ac, 3~
55 A rms, max
60 A rms
16 mm^2 (AWG 6)
390AFX-4
380/400 V ac, 3~
480 V ac, 3~
20 A rms, max
16 A rms, max
25 A rms
20 A rms
6 mm^2 (AWG 10)
4 mm^2 (AWG 12)
3120AFX-4
380/400 V ac, 3~
480 V ac, 3~
27 A rms, max
22 A rms, max
30 A rms
25 A rms
6 mm^2 (AWG 10)
6 mm^2 (AWG 10)
3150AFX-4
380/400 V ac, 3~
480 V ac, 3~
30 A rms, max
24 A rms, max
35 A rms
30 A rms
10 mm^2 (AWG 8)
6 mm^2 (AWG 10)
Table 5-1: AC Input Wire Size Table