AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 293 of 485
Query Format
[SOURce:]MODE#?
Description
Returns protection mode for the selected phase # (# = 1, 2, or 3). If #
is omitted, returns protection mode for all phases in comma
separated format.
Note: When the phase suffix is 1, 2 or 3 the possible return
categories are from 0 to 4. With suffix is omitted, this command will
return MIXED(5) if modes for each phase are not the same.
For example, if in split phase mode phase A (suffix 1) is in VOLTAGE
mode but phase B (suffix 2) is in CURRENT mode, the query
SOUR:MODE? you will return MIXED:
SOUR:MODE1? = VOLTAGE and SOUR:MODE2? = CURRENT ->
SOUR:MODE? = MIXED
If both or phases are set to the same mode, the actual mode will be
returned:
SOUR:MODE1? = VOLTAGE and SOUR:MODE2? = VOLTAGE ->
SOUR:MODE? = VOLTAGE
Returned Data Format
<cr>
Available protection modes:
0 = NONE
1 = VOLTAGE
2 = CURRENT
3 = POWER
4 = KVA
5 = MIXED
Query Example
SOUR:MODE?
VOLTAGE, VOLTAGE, VOLTAGE
Command Syntax
[SOURce:]PROTect[:RMS]:POWer[:STATe] <ON|OFF>
Description
This command turns the true power protection on or off.
Parameters
< 0 | OFF | 1 | ON >
Parameter Format
<b> | <cr>
Example
PROT:POW ON
Query Format
[SOURce:]PROTect[:RMS]:POWer[:STATe]?
Returned Data Format
<b>
Query Example
PROT:POW?
1
Command Syntax
[SOURce:]PROTect[:RMS]:POWer:LEVel <LEVEL>
Description
This command sets the true power protection trip level. Setting is in
KW.
Parameters
< LEVEL >
Parameter Format
<nr2>
Example
PROT:POW:LEV 5
Query Format
[SOURce:]PROTect[:RMS]:POWer:LEVel?
Returned Data Format
<b>
Query Example
PROT:POW:LEV?
5.000