AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 228 of 485
Command Syntax
MEASure:LOGger:RATE
Description
Sets the frequency at which the logging process will take
measurements.
Parameters
Frequency in Hz. Range is 1 Hz through 10 Hz.
Parameter Format
<nr1>
Example
MEAS:LOG:RATE 5
Query Format
MEASure:LOGger:RATE?
Returned Data Format
<nr1>
Query Example
MEAS:LOG:RATE?
5
Command Syntax
MEASure:LOGger:TIMEstamp <cr>
Description
Sets the time stamp format that will be attached to every
measurement record in the measurement log file.
Parameters
< DATE | 0 | TIME | 1 | ALL | 2 >
Parameter Format
<cr>
Example
MEAS:LOG:TIME ALL
Query Format
MEASure:LOGger:TIMEstamp?
Returned Data Format
<nr1>
Query Example
MEAS:LOG:TIME?
2
Содержание AFX Series
Страница 484: ......