AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 321 of 485
8.7.12
PULSE Transient Commands
The command in this section control PULSE transients. Some of these commands have the
option to specify NORmal or SATurate.
SATurate mode:
If a dwell time setting is out of limits, the dwell time will saturate to the
limit min/max and it will not trip an error.
NORmal mode
:
If a dwell time setting is out of limits, an error will be generated and
the dwell time setting will not be modified.
Command Syntax
[SOURce:]PULSe:COUNT <nr1>, <opt>
Description
This command sets the pulse count or the number of pulses to
execute. Minimum time set value allowed is 1.
Parameters
Count, Option: < NORmal | SATurate >
Default is NORmal if optional second parameter is omitted.
Parameter Format
<nr1>, <cr>
Example
PULS:COUNT 5
Query Format
[SOURce:]PULSe:COUNT?
Returned Data Format
<nr1>
Query Example
PULS:COUNT?
5.0000
Query Syntax
[SOURce:]PULSe:COUNT:MINimum?
Description
This command returns the minimum permissible set value for the
PULSE count.
Returned Data Format
<nr1>
Query Example
PULS:COUNT:MIN?
0
Query Syntax
[SOURce:]PULSe:COUNT:MAXimum?
Description
This command returns the maximum permissible set value for the
PULSE count.
Returned Data Format
<nr1>
Query Example
PULS:COUNT:MAX?
65535
Query Syntax
[SOURce:]PULSe:COUNT:DEFault?
Description
This command returns the default set value for the PULSE count.
Returned Data Format
<nr1>
Query Example
PULS:COUNT:DEF?
1